© 2013 UTC Fire & Security. All rights reserved. 1 / 2 P/N 3101190 • REV 03 • REB 25JAN13
E-IDC1B Analog Single Input Mini Module
Installation Sheet
Operation
The E-IDC1B Analog Single Input Mini Module is an analog
addressable device used to connect a normally open, alarm,
supervisory, or monitor type dry contact initiating device
circuit (IDC) to a control panel. This module is designed for
Class B circuit operation.
The device address is set using the two rotary switches
located on the front of the module. One device address is
required.
The module is factory set to operate as an alarm-latching
device. When the NO contact of an initiating device is
closed, an alarm signal is sent to the control panel and the
alarm condition is latched at the module.
Additional device types are available through front panel
programming or the configuration utility. For additional
information, refer to the documents listed on the control
panel label.
LEDs
The provides two status LEDs. The LEDs are visible from
the back of the module.
Figure 1: LED location
21
1. Red LED: Alarm/active
2. Green LED: Normal
Installation
WARNINGS
This module does not operate without electrical power.
As fires frequently cause power interruption, discuss
further safeguards with the local fire protection
specialist.
This module does not support conventional two-wire
smoke detectors.
Note: The module is shipped from the factory as an
assembled unit; it contains no user-serviceable parts and
should not be disassembled.
To install the module:
1. Verify that all field wiring is free of opens, shorts, and
ground faults.
2. Make all wiring connections as discussed in “Wiring
and shown in Figure 3.
3. Set the required device address. For example, to set the
device address for 21, set the TENS switch (marked 0
to 12) to 2 and the ONES switch (marked 0 to 9) to 1.
See Figure 2.
The devices can be addressed from 01 to 129. Panel
addressing may vary.
4. Position the module into the electrical box, behind the
device to which it connects.
Figure 2: Module address
1
0
1
2
3
4
5
6
12
11
10
9
8
7
0
9
1
2
3
4
5
6
7
8
1. Insert screwdriver here
Page view 0
1 2

Summary of Contents

Page 1 - Installation Sheet

© 2013 UTC Fire & Security. All rights reserved. 1 / 2 P/N 3101190 • REV 03 • REB 25JAN13 E-IDC1B Analog Single Input Mini Module Installation

Page 2 - Contact information

2 of 2 P/N 3101190 • REV 03 • ISS 25JAN13 Wiring Wire in accordance with NFPA 72 and CAN/ULC-S524, Standard for the Installation of Fire Alarm Sys